Specification
Current Load: 150 mA max @ 32 VDC
Dimensions (H x W x D): 11.99 x 5.1 x 10.62 cm 4.72 x 2.0 x 4.18 in
Shipped with Each Unit: One - J180 screw terminal plug
Ethernet Ports (E1, E2): 10/100 Base-T half duplex RJ45 Connector Link and Activity LED indicators Electrical Isolation 1500 V rms at 50 to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
Shock: IEC 60068-2-27; 30G @ 18ms (Non-Operational)
Power Supply: 10 to 36 VDC power input allowed
Current Load: 200 mA max @ 24 VDC
Power Supply: 2.5 mm screwdriver blade
Power Supply: Positive, Negative, GND Terminals
Shock: IEC 60068-2-27; 15G @ 11ms (Operational)
Current Load: 450 mA max @ 10 VDC
Shipped with Each Unit: One - Ethernet straight-through cables
Shipped with Each Unit: One - ProSoft Solutions DVD
Operating Temperature: -25°C to 70°C (-13°F to 158°F)
Ethernet Ports (E1, E2): Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
Relative Humidity: 5% to 95%, with no condensation
Storage Temperature: -40°C to 85°C (-40°F to 185°F)
Power Supply: 24 VDC nominal
Vibration: IEC 60068-2-6; 5G, 10 to 150 Hz
LED Indicators: ERR, CFG, FLT, PWR
Shipped with Each Unit: One - HRD250 screwdriver
EtherNet/IP Server
Class 1 Messaging: I/O connections for real-time data transfer
Class 3 Messaging: PLC messaging support
ACSI Basic Conformance
SCSMs supported: SCSM: IEC 61850 8.1(MMS) used
ACSI Model Conformance
GOOSE: SBO-with-Enhanced-Security
Status Data: High-level status data available from Ethernet/IP
GOOSE: Direct-with-Enhanced-Security
Status Data: Client through the Ethernet/IP Server (for example PLC or PAC)
Configurable Parameters: MMS Command Delay
Reporting: Unbuffered Report Control Block (URCB)
Reporting: Buffered Report Control Block (BRCB)
Status Data: Report and GOOSE status available
GOOSE: Direct-with-Normal-Security
Status Data: Status available per node
Logical Nodes: IEC 61850 Logical Nodes, including Logical Nodes for Hydro Power Plants and Logical Nodes for Wind Power Plants
GOOSE: SBO-with-Normal-Security
SNTP/NTP Client
Configurable Parameters: SNTP/NTP server address
Configurable Parameters: SNTP/NTP server synchronization rate in minutes
The ProSoft Technology® EtherNet/IP™ to IEC 61850 communication gateway allows Rockwell Automation® PACs to interface with IEC 61850 Intelligent Electronic Devices (IED) such as substation power monitors and relays. The gateway acts as an IEC 61850 Client polling the devices on your network. The two ports allow the IEC 61850 and EtherNet/IP™ protocols to reside on separate subnets.