Specification
EtherNet/IP Specifications
Class 3 Client Connections: Unconnected - 1
EtherNet/IP Specifications
Command List: Support for 100 commands per Client, each configurable for command type, IP address, register to/from addressing and word/bit count.
Supported PLC Types: PLC2, PLC5, SLC, CLX, CMPLX, MICROLX
Max RPI time: 5 ms per connection
Command Sets: PLC5 ASCII Command Set
Command Sets: PLC5 Binary Command Set
Number of Class 1 I/O Connections: 8
Number of Class 3 Server Connections: 5
Class 3 Client Connections: Connected - 2
CIP Services Supported: 0x4D - CIP Data Table Write
Supported Message Types: PCCC and CIP
Command Sets: PLC-2/PLC-3/PLC5 Basic Command Set
CIP Services Supported: 0x4C - CIP Data Table Read
Command Sets: SLC500 Command Set
I/O connection sizes in/out: 496/496 bytes
PROFINET Specifications
Driver Type: Class A Device
PROFINET I/O Data: 1440 bytes IN, 1440 bytes OUT
Exchange Types: Cyclic Real-time (RT) and Acyclic Data
Environmental
Shipped With Each Unit: 2.5 mm screwdriver
Ethernet Ports (2): 10/100Mbit RJ45 Connector Electrical Isolation 1500 Vrms at 50 Hz to 60 Hz for 60 seconds, applied as specified in section 5.3.2 of IEC 60950: 1991
Dimensions (H x W x D): 5.38 x 1.99 x 4.38 in 13.67 x 5.05 x 11.13 cm
Relative Humidity: 5% to 95% RH with no condensation
Current Load: 24 VDC nominal @ 300 mA
Ethernet Ports (2): Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
Current Load: 10 to 36 VDC @ 610 mA maximum
Power Supply: 24 VDC nominal
Storage Temperature: -40°C to 80°C (-40°F to 176°F)
Power Supply: Positive, Negative, GND Terminals
Shipped With Each Unit: ProSoft Solutions DVD
Shipped With Each Unit: 5’ straight-through Ethernet cable
Shock: IEC 60068-2-27; 30G @ 18ms, 3-Axis (Non-Operation)
Operating Temperature: -25°C to 70°C (-13°F to 158°F)
Shock: IEC 60068-2-27; 15G @ 11ms, 3-Axis (Operational)
Shipped With Each Unit: J180 Power Connector
Power Supply: 10 to 36 VDC allowed
Vibration: IEC 60068-2-6; 5G @ 10Hz to 150Hz
The EtherNet/IP to PROFINET device gateway offers bi-directional data transfers between a PROFINET Controller and EtherNet/IP networks. The PLX32-EIP-PND gateway is a stand-alone DIN-rail mounted unit that provides two Ethernet ports, with each port using a different subnet. The onboard SD Card slot (SD card optional) is used for storing configuration files that can be used for recovery, transferring the configuration to another gateway, or general configuration backup. The EtherNet/IP Driver uses Class 1 I/O connections or Class 3 Message instructions. The PROFINET driver operates as a PROFINET Class A device.