Specification
Current Load: 10 to 36 VDC @ 610 mA maximum
Power Supply: 10 to 36 VDC allowed
Storage Temperature: -40°C to 80°C (-40°F to 176°F )
Dimensions (H x W x D): 5.38 x 1.99 x 4.38 in 13.67 x 5.05 x 11.13 cm
Operating Temperature: -25°C to 70°C (-13°F to 158°F )
Current Load: 24 VDC nominal @ 300 mA
Power Supply: Positive, Negative, GND Terminals
Power Supply: 24 VDC nominal
Vibration: IEC 60068-2-6; 5G @ 10 to 150 Hz
Relative Humidity: 5% to 95% RH with no condensation
Shock: IEC 60068-2-27; 15G @ 11ms, 3-Axis (Operational)
Shock: IEC 60068-2-27; 30G @ 18ms, 3-Axis (Non-Operational)
Modbus TCP/IP Specifications
Command List Polling: Each command can be individually enabled or disabled; write-only-on-data-change is available
Supported Modbus Function Codes: Mask Write Holding Register (server only)
Status Data: Error codes reported individually for each command
Supported Modbus Function Codes: Read Input Registers
Command List: Up to 160 fully configurable client commands
Supported Modbus Function Codes: Read Coil Status
Supported Modbus Function Codes: Preset (Write) Multiple Holding Registers
Supported Modbus Function Codes: Force (Write) Single Coil
Supported Modbus Function Codes: Preset (Write) Single Holding Register
Supported Modbus Function Codes: Read/Write Holding Registers (server only)
Supported Modbus Function Codes: Read Holding Registers
Supported Modbus Function Codes: Read Input Status
Supported servers: MBAP = 5, Encapsulated = 5
Supported Modbus Function Codes: Force (Write) Multiple Coils
Supported clients: 10
PROFINET Specifications
Driver Type: Class A Device
Exchange Types: Cyclic Real-time (RT) and Acyclic Data
PROFINET I/O Data: 1440 bytes IN, 1440 bytes OUT
The Modbus TCP/IP to PROFINET device gateway offers bi-directional data transfer between a PROFINET Controller and Modbus TCP/IP networks. The Modbus TCP/IP driver uses multiple clients and servers for faster data throughput. The PROFINET driver operates as a PROFINET device (slave). The PLX31-MBTCP-PND gateways are stand-alone DIN-rail mounted units that provide one Ethernet port for communications, remote configuration, and diagnostics. The onboard SD Card slot (SD card optional) is used for storing configuration files that can be used for recovery, transferring the configuration to another gateway, or general configuration backup.