Specification
Number of Class 3 Server Connections: 5
CIP Services Supported: 0x4D - CIP Data Table Write
Max I/O connection sizeIn/Out: 496/496 bytes
Supported PLC Types: PLC2, PLC5, SLC, CLX, CMPLX
Number of Class 1 I/O Connections: 8
Max RPI time: 10 ms per connection
Supported Message Types: PCCC and CIP
Command Sets: PLC5 ASCII Command Set
Command List: Support for 100 commands per Client, each configurable for command type, IP address, register to/from addressing and word/bit count.
Command Sets: SLC500 Command Set
Number of Class 3 Client Connections: Unconnected - 1
Command Sets: PLC5 Binary Command Set
Command Sets: PLC-2/PLC-3/PLC5 Basic Command Set
CIP Services Supported: 0x4C - CIP Data Table Read
Number of Class 3 Client Connections: Connected - 2
LED Indicators: Configuration (CFG), Error (ERR), Power (PWR), Hardware Fault (FLT), Network Status (NS), EtherNet/IP™ Class I or Class III Connection Status (EtherNet/IP Only) Module Status (MS), ModuleConfiguration Status (EtherNet/IP Only) Ethernet Communication Port Link/Activity, and 100 mbit
Current Load: 10 to 36 VDC @ 610 mA maximum
Power Supply: 10 to 36 VDC allowed
Power Supply: 24 VDC nominal
Dimensions (H x W x D): 5.38 x 1.99 x 4.38 in 13.67 x 5.05 x 11.13 cm
Shipped With Each Unit: ProSoft Solutions DVD
Storage Temperature: -40°C to 80°C (-40°F to 176°F)
Shipped With Each Unit: 2.5 mm screwdriver
Current Load: 24 VDC nominal @ 300 mA
Shock: IEC 60068-2-27; 30G @ 18ms, 3-Axis (Non-Operational)
Ethernet Port: 10/100Mbit half-duplex RJ45 Connector Electrical Isolation 1500 Vrms at 50 to 60 Hz for 60 seconds, applied as specified in section 5.3.2 of IEC 60950: 1991 Ethernet Broadcast Storm Resiliency is less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
Shipped With Each Unit: 5’ straight-through Ethernet cable
Power Supply: Positive, Negative, GND Terminals
Relative Humidity: 5% to 95% RH with no condensation
Operating Temperature: -25°C to 70°C (-13°F to 158°F)
Vibration: IEC 60068-2-6; 5G @ 10 to 150 Hz
Shipped With Each Unit: J180 Power Connector
Shock: IEC 60068-2-27; 15G @ 11ms, 3-Axis (Operational)
The EtherNet/IP™ to PROFINET® IO Device (slave) gateway offers bi-directional data transfers between EtherNet/IP™ controllers and a PROFINET® IO controller. The EtherNet/IP™ Driver supports I/O connections for guaranteed data delivery or Message instructions to send data to/from the PACs. The gateway supports 1440 bytes of input data and 1440 bytes of output data for larger applications. In addition, the gateway’s multiple I/O connections, allow you to set different RPIs for control data and module diagnostics, enabling you to optimize your Ethernet bandwidth.