Ethernet Port (Ethernet modules): 10/100 Base-T
RJ45 Connector
Link and activity LED indicators
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as
specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-
per-second and less than or equal to 5 minutes duration
CFG Port (CFG): RJ45 (DB-9M with supplied cable)
RS-232 only
No hardware handshaking
Shipped with Unit: RJ45 to DB-9M cables for each port
6-foot RS-232 configuration cable
BackPlane Current Load: 800 mA @ 5.1 VDC
3 mA @ 24 VDC
Storage Temperature: -40° F to 185° F (-40° C to 85° C)
Shock: 30 g Operational
50 g non-operational
Vibration: 5 g from 10 to 150 Hz
Relative Humidity: 5% to 95% (without condensation)
LED Indicators: Module Status
Backplane Transfer Status
Application Status
Serial Activity
Enclosure: Aluminium
Sub Brand: MV56
Type: Communication Module
Special Features: Single Slot - 1756 backplane compatible,The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module,Ladder Logic is used for data transfer between module and processor. Sample ladder file included,Configuration data obtained from configuration text file downloaded to module. Sample configuration file included, Local or remote rack
Application: Power, Petrochemical, Water Treatment, Oil and Gas Production
Standard: EX Certificate; CB Safety; CE Mark; GOST-R; Korean KC Registration; Registro Italiano Navale; UL/cUL; Class 1. Div 2; UL/cUL; Class 1, Div 2
_Ethernet: 10/100 Base-T
Communication: IEC 60870-5-104 Server Network
Isolation: 500 V
Alarm Contacts: LED
Interface: RS-232, 485 and 422
Power Supply: 800 mA @ 5 V DC, 3mA @ 24V DC,
Mounting: Rack
Operating Temperature: 32° F to 140° F (0° C to 60° C)
Brand Name: PROSOFT
The MVI56 IEC 60870-5-104 Server Network Interface Module allows ControlLogix processors to interface easily with IEC 60870-5-104 protocol-compatible hosts. The MVI56-104S module has been designed to address applications where a device using the IEC 60870-5-104 protocol needs to communicate with a ControlLogix processor. Functionality of the IEC protocol is very similar to the DNP 3.0 protocol which features time stamping and True Report by Exception (TRBE). These features allow the MVI56-104S module to send a report to the processor without being polled, providing real time data transmission in critical situations.