Storage Temperature: -40° F to 185° F (-40° C to 85° C)
Shock: 30 g Operational
50 g non-operational
Vibration: 5 g from 10 to 150 Hz
Relative Humidity: 5% to 95% (without condensation)
LED Indicators: Module Status
Backplane Transfer Status
Application Status
Serial Activity
CFG Port (CFG): RJ45 (DB-9M with supplied cable)
RS-232 only
Software configurable communication parameters: Baud rate: 110 to 115,200 baud, depending on protocol
RS-232, 485 and 422
Parity: none, odd or even
Data bits: 5, 6, 7, or 8
Stop bits: 1 or 2
RTS on/off delay: 0 to 65535 milliseconds
App Ports (P1,P2) (Serial modules): RJ45 (DB-9M with supplied cable)
RS-232 handshaking configurable
500 V Optical isolation from backplane
Shipped with Unit: RJ45 to DB-9M cables for each port
6-foot RS-232 configuration cable
BackPlane Current Load: 800 mA @ 5.1 VDC
3 mA @ 24 VDC
Operating Temperature: 32° F to 140° F (0° C to 60° C)
Brand Name: PROSOFT
Sub Brand: MV56
Type: Communication Module
Special Features: Single Slot - 1756 backplane compatible,The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module,Ladder Logic is used for data transfer between module and processor. Sample ladder file included,Configuration data obtained from configuration text file downloaded to module. Sample configuration file included, Local or remote rack
Application: Power and Distribution Applications, Petrochemical, Water and Gas Applications, Oil and Gas Production
Standard: EX Certificate; CB Safety; CE Mark; GOST-R; Russian GOST-R; Korean KC Registration; UL/cUL; Class 1 Div 2; UL/cUL; Class1 Div (Canada)
Number Of Channels: 10/100 Base-T
Communication: IEC 60870-5-101 Slave
Isolation: 500 V
Alarm Contacts: LED
Enclosure: Aluminium
Interface: RS-232, 485 and 422
Power Supply: 800 mA @ 5 V DC, 3mA @ 24V DC,
Mounting: Rack
The MVI56 IEC 60870-5-101 Slave Network Interface Module is the fastest and easiest way to add IEC 60870-5-101 protocol interface connectivity for the ControlLogix platform. The module has two powerful and highly configurable IEC 60870-5-101 Slave ports, allowing the many SCADA and field devices supporting the IEC protocol to be integrated into the ControlLogix platform. The MVI56-101S is designed to address applications where a host system using the IEC 60870-5-101 protocol must communicate with a ControlLogix processor. Functionality of the IEC protocol is very similar to the DNP 3.0 protocol which features time stamping and True Report by Exception (TRBE). These features allow the MVI56-101S module to send a report to the processor without being polled, providing real time data transmission in critical situations.