LED Indicators: Module status, Backplane transfer status, Application status, Serial activity
(debug port), Ethernet link and activity, and error LED status
Configuration Connector: RJ45 RS‑232 Connector (RJ45 to DB-9 cable shipped with unit)
CFG Port (CFG): RJ45 (DB-9M with supplied cable)
RS-232 only
No hardware handshaking
_Ethernet: 10/100 Base-T
Standard: CE Mark; GOST-R; Korean KC Registration; UL/cUL; Class1. Div 2; UL/cUL; Class1, Div 2
Application: Food Processing, Petrochemical, Pulp and Paper, Automobile Manufacturing, Water and Wastewater, Oil and Gas, Power and Electric
Special Features: Single Slot Backplane Compatible, Ladder Logic is Used for Data Transfer Between Module and Processor, Sample Ladder File Included, Backplane Current Load:800MILAMP at 5V, Vibration:5g From 10150HZ, , Port: Ethernet
Type: Communication Module
Sub Brand: MV46
Brand Name: PROSOFT
Ethernet Port (Ethernet modules): RJ45 Connector
Link and activity LED indicators
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 seconds, applied as
specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-
per-second and less than or equal to 5 minutes duration
BackPlane Current Load: 800 mA @ 5.1 VDC
Operating Temperature: 32° F to 140° F (0° C to 60° C)
Storage Temperature: -40° F to 185° F (-40° C to 85° C)
Relative Humidity: 5% to 95% (without condensation)
Shock: 30 g operational, 50 g non-operational
Vibration: 5 g from 10 to 150 Hz
Processor: Compatible with Rockwell Automation SLC 5/02 M0/M1 capable processors or newer
The MVI46 Modbus TCP/IP Network Interface Module is designed to allow SLC processors to interface easily with other Modbus TCP/IP protocol-compatible devices using client and server functionality. Compatible devices include not only Modicon processors (which support the Modbus TCP/IP protocol) but also a wide assortment of other clients and server devices.