Power Supply: 24 VDC nominal
18 to 32 VDC allowed
Positive, Negative, GND Terminals
2.5 mm screwdriver blade
Current Load: 500 mA max @ 32 VDC max
Operating Temperature: -4° F to 122° F (-20° C to 50° C)
Storage Temperature: -40° F to 185° F (-40° C to 85° C)
Relative Humidity: 5% to 95% (with no condensation )
Application Ports: Modbus Plus Connector
Two DB9 Female Standard Modbus Plus connectors
Serial Port Isolation: 2500 V RMS port signal isolation per UL 1577
3000 VDC min. port to ground and port to logic power isolation
Shipped with Each Unit: Mini-DIN to DB-9M serial cables
4 ft RS-232 configuration cable
2.5mm screwdriver
CD (docs and Configuration utility)
RS-422/485 DB-9 to Screw Terminal Adaptor (1 or 4, depending on ports)
Dimensions: Standard:
5.20 in H x 2.07 in W x 4.52 in D (13.2 cm x 5.25 cm x 11.48 cm)
Extended:
5.20 in H x 2.73 in W x 4.52 in D
(13.2 cm x 6.934 cm x 11.48 cm)
LED Indicators: Power and Module Status
Application Status
Serial Port Activity
Serial Port Error Status
Ethernet Port (Ethernet modules only): 10Base-T half duplex RJ45 Connector
Link and Activity LED indicators
Electrical Isolation 1500 V RMS at 50 Hz to 60 Hz for 60 s, applied as
specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-
per-second and less than or equal to 5 minutes duration
Configuration Serial Port: DB-9M RS-232 only
No hardware handshaking
Brand Name: PROSOFT
Sub Brand: 5000
Type: Stand-alone Gateway
Special Features: Ideal solution for applications where Modbus Plus connectivity can be used to integrate a PROFIBUS DP master device into a system; Powerful module designed with both Master and Slave support, enabling easy connection to other Modbus devices (Modicon processors and many others).
Application: Manufacturing, Oil and Gas, Electrical Power and Food Processing.
Standard: ATEX, CE/EMC, Environmental, UL,GOST-R
Ethernet: 10Base-T
Interface: RS-232, RS-422, RS-485
Port: 2
Configuration: Yes
Frequency Rating: 50 to 60
Connectivity: Serial
Protocol: PDPS, MCM
Software Requirements: Drivers
Enclosure: Aluminum
Length: 4.52
Width: 2.07
Height: 5.2
Environmental Conditions: -20 to 50DEG C Operating, -40 to 85DEG C Storage, 5 to 95 Percent Humidity
The ProLinx Modbus Plus to PROFIBUS DP Slave Gateway creates a powerful connection between devices on a Modbus Plus network and a PROFIBUS master device. This stand-alone DIN-rail mounted protocol gateway provides one Modbus Plus configurable DB9F port and PROFIBUS DP Slave configurable DB9F port. The Modbus Plus protocol driver supports both Master and Slave implementations of the protocol on the DB9 Female Modbus Plus port. The Modbus Plus port is fully configurable. The PROFIBUS DP Slave protocol driver supports the PROFIBUS V0 Slave implementation, providing powerful data transfer capability between the ProLinx module and Siemens PLCs or other hosts. User configurable data mapping and DP port operation make the interface an easy to use and powerful data transfer tool.