Dimensions: Standard:
5.20 in H x 2.07 in W x 4.52 in D (13.2 cm x 5.25 cm x 11.48 cm)
Extended:
5.20 in H x 2.73 in W x 4.52 in D
(13.2 cm x 6.934 cm x 11.48 cm)
LED Indicators: Power and Module Status
Application Status
Serial Port Activity
Serial Port Error Status
Shipped with Each Unit: Mini-DIN to DB-9M serial cables
4 ft RS-232 configuration cable
2.5mm screwdriver
CD (docs and Configuration utility)
RS-422/485 DB-9 to Screw Terminal Adaptor (1 or 4, depending on ports)
Configuration Serial Port: DB-9M RS-232 only
No hardware handshaking
Ethernet Port (Ethernet modules only): 10Base-T half duplex RJ45 Connector
Link and Activity LED indicators
Electrical Isolation 1500 V RMS at 50 Hz to 60 Hz for 60 s, applied as
specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-
per-second and less than or equal to 5 minutes duration
Application Ports: Modbus Plus Connector
Two DB9 Female Standard Modbus Plus connectors
Serial Port Isolation: 2500 V RMS port signal isolation per UL 1577
3000 VDC min. port to ground and port to logic power isolation
Power Supply: 24 VDC nominal
18 to 32 VDC allowed
Positive, Negative, GND Terminals
2.5 mm screwdriver blade
Current Load: 500 mA max @ 32 VDC max
Operating Temperature: -4° F to 122° F (-20° C to 50° C)
Storage Temperature: -40° F to 185° F (-40° C to 85° C)
Relative Humidity: 5% to 95% (with no condensation )
Enclosure: Aluminum
Width: 2.07
Height: 5.2
Environmental Conditions: -20 to 50DEG C Operating, -40 to 85DEG C Storage, 5 to 95 Percent Humidity
Brand Name: PROSOFT
Sub Brand: 5000
Type: Stand-alone Gateway
Special Features: Ideal solution for applications where Modbus Plus connectivity can be used to integrate a PROFIBUS DP slave device into a system; Powerful module designed with both Master and Slave support, enabling easy connection to other Modbus devices (Modicon processors and many others).
Standard: ATEX, CE/EMC, Environmental, UL,GOST-R
Ethernet: 10Base-T
Interface: RS-232, RS-422, RS-485
Port: 3
Configuration: Yes
Frequency Rating: 50 to 60
Connectivity: Serial
Protocol: MCM
Software Requirements: Drivers
Length: 4.52
The ProLinx Modbus Plus to PROFIBUS DPV1 Master Gateway creates a powerful connection between devices on a Modbus Plus network and a PROFIBUS slave device. This stand-alone DIN-rail mounted protocol gateway provides one Modbus Plus configurable DB9F port and one PROFIBUS DPV1 Master configurable DB9F port. The Modbus Plus protocol driver supports both Master and Slave implementations of the protocol on the DB9 Female Modbus Plus port. The Modbus Plus port is fully configurable. The PROFIBUS DP Master protocol driver supports complete Master specifications according to IEC 61158 on either a Mono-Master or Multi-Master network. The module supports the DPV1 specification.