Ethernet Port (Ethernet modules only): 10Base-T half duplex RJ45 Connector
Link and Activity LED indicators
Electrical Isolation 1500 V RMS at 50 Hz to 60 Hz for 60 s, applied as
specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-
per-second and less than or equal to 5 minutes duration
Application Ports: Modbus Plus Connector
Two DB9 Female Standard Modbus Plus connectors
Power Supply: 24 VDC nominal
18 to 32 VDC allowed
Positive, Negative, GND Terminals
2.5 mm screwdriver blade
Current Load: 500 mA max @ 32 VDC max
Shipped with Each Unit: Mini-DIN to DB-9M serial cables
4 ft RS-232 configuration cable
2.5mm screwdriver
CD (docs and Configuration utility)
RS-422/485 DB-9 to Screw Terminal Adaptor (1 or 4, depending on ports)
Operating Temperature: -4° F to 122° F (-20° C to 50° C)
Dimensions: Standard:
5.20 in H x 2.07 in W x 4.52 in D (13.2 cm x 5.25 cm x 11.48 cm)
Extended:
5.20 in H x 2.73 in W x 4.52 in D
(13.2 cm x 6.934 cm x 11.48 cm)
Storage Temperature: -40° F to 185° F (-40° C to 85° C)
LED Indicators: Power and Module Status
Application Status
Serial Port Activity
Serial Port Error Status
Relative Humidity: 5% to 95% (with no condensation )
Configuration Serial Port: DB-9M RS-232 only
No hardware handshaking
Serial Port Isolation: 2500 V RMS port signal isolation per UL 1577
3000 VDC min. port to ground and port to logic power isolation
Special Features: Ideal solution for applications where PROFIBUS connectivity can be used to integrate DF1 devices into a system; Powerful module designed with Server support, enabling easy connection to Rockwell Automation PLCs (CLX, SLC, PLC, CPLX, and similar devices).
Application: Manufacturing, Oil and Gas, Electrical Power and Food Processing.
Standard: ATEX, CE/EMC, Environmental, UL,GOST-R
Ethernet: 10Base-T
Interface: RS-232, RS-422, RS-485
Port: 2
Data Transfer Rate: 110 to 115
Configuration: Yes
Brand Name: PROSOFT
Sub Brand: 5000
Type: Stand-alone Gateway
Frequency Rating: 50 to 60
Connectivity: Serial
Protocol: PDPS
Software Requirements: Drivers
Enclosure: Aluminum
Length: 4.52
Width: 2.07
Height: 5.2
Environmental Conditions: -20 to 50DEG C Operating, -40 to 85DEG C Storage, 5 to 95 Percent Humidity
The ProLinx DF1 Master/Slave to PROFIBUS DP Slave Gateway creates a powerful connection between devices on a PROFIBUS DP network and DF1 devices. This stand-alone DIN-rail mounted protocol gateway provides one serial port and one PROFIBUS DP Slave. The DF1 protocol driver supports Master or Slave implementations of the protocol on each DF1 port. All DF1 ports are individually configurable. The PROFIBUS DP Slave protocol driver supports the PROFIBUS V0 Slave implementation, providing powerful data transfer capability between the ProLinx module and Siemens PLCs or other hosts. User configurable data mapping and DP port operation make the interface an easy to use and powerful data transfer tool.