Software configurable Comunicação parameters: taxa de transmissão: 110 transmissão to 115.2kbps
RS-232, 485 e 422
Parity: Nenhum, odd Ou even
Data bits: 5, 6, 7, 8
Stop bits: 1 Ou 2
RTS on/off delay: 0 to 65535 milliseconds
Serial Applications Portas (P1, P2): RJ45 (DB-9M com supplied adapter cable)
Configurable RS-232 hardware heshaking
500V Optical Isolamento from barramento
RS-232, RS-422, RS-485 jumper-select, each port
RX (Receive) e TX (Transmit) LEDs, each port
Humidade relativa: 5 to 95% (without condensing)
Indicadores LED: Battery Status (ERR)
Aplicação Status (APP)
Módulo Status (OK)
Shipped com Unit: RJ45 to DB-9M cables for each Porta serial
5 foot Ethernet Straight-Thru Cable (Cinza)
4-Character, Scrolling, Alpha-Numeric LED Visor: Shows Módulo, Version, IP, Port Master/SlaveSetting, Port Status, e Error
Information
Porta ethernet: 10/100 Base-T, RJ45 Conector, for CAT5 cable
Link e Activity Indicadores LED
Auto-crossover cable detection
barramento Current Load: 800 mA @ 5 Vcc, 3 mA @ 24 Vcc
Temperatura de operação: 0°C to 60°C (32°F to 140°F) - MVI56E-MCM
-25°C to 70°C (-13°F to 158°F) - MVI56E-MCMXT
Temperatura de armazenamento: -40°C to 85°C (-40°F to 185°F)
Choque:: 30g Operational
50g non-operational
Vibração: 5 g from 10 to 150 Hz
Ato como módulo de entrada / saída no painel traseiro do ControlLogix. Duas portas seriais independentemente configuráveis pode operar sobre os mesmos ou diferentes redes Modbus. Cada porta pode ser configurada como um Modbus mestre ou o escravo, compartilhando a mesma palavra-5000 controlado pelo utilizador