Características especiais: Ideal solution for applications where Modbus Plus Conectividade can be used to integrate a PROFIBUS DP slave device into a system; Powerful Módulo designed com both Master e Slave support, enabling easy Conexão to Outros Modbus Dispositivos (Modicon processors e many Outross).
Porta ethernet (Modulos ethernet only): 10Base-T half duplex RJ45 ConectOu
Link e Activity IndicadOues LED
Electrical Isolamento 1500 V RMS at 50 Hz to 60 Hz fOu 60 s, applied as
specified in section 5.3.2 De IEC 60950: 1991
Ethernet Broadcast StOum Resiliency = less than Ou equal to 5000 [ARP] frames-
per-second e less than Ou equal to 5 minutes duration
Aplicação Portas: Modbus Plus Conector
Two DB9 Fêmea Padrão Modbus Plus Conectores
Porta serial Isolamento: 2500 V RMS port Sinal Isolamento per UL 1577
3000 Vcc min. port to ground e port to logic potência Isolamento
Shipped com Each Unit: Mini-DIN to DB-9M serial cables
4 ft RS-232 Configuração cable
2.5mm Parafusodriver
CD (docs e Configuração utility)
RS-422/485 DB-9 to Parafuso Terminal AdaptOu (1 Ou 4, depending on POutas)
Dimensões: Padrão:
5.20 in H x 2.07 in W x 4.52 in D (13.2 cm x 5.25 cm x 11.48 cm)
Estendido:
5.20 in H x 2.73 in W x 4.52 in D
(13.2 cm x 6.934 cm x 11.48 cm)
Indicadores LED: potência e Módulo Status
Aplicação Status
Porta serial Activity
Porta serial Estado de erro
Configuração Porta serial: DB-9M RS-232 only
No hardware handshaking
Fonte de Alimentação: 24 Vcc nominal
18 to 32 Vcc allowed
Positive, Negative, GND Terminals
2.5 mm screwdriver blade
Current Load: 500 mA max @ 32 Vcc max
Temperatura de operação: -4° F to 122° F (-20° C to 50° C)
Temperatura de armazenamento: -40° F to 185° F (-40° C to 85° C)
Humidade relativa: 5% to 95% (sem condensação )
Protocol: TCP/IP, MBP
Invólucro: Aluminum
Aplicação: Manufacturing, Oil e Gas, Electrical potência e Food Processing.
Padrão: ATEX, CE/EMC, Environmental, UL,GOST-R
Ethernet: 10Base-T
Interface: RS-232, RS-422, RS-485
Port: 2
Configuração: Yes
Classificação de frequência: 50 to 60
Conectividade: Serial
Software Requirements: Drivers
Comprimento: 4.52
Tamanho: 2.07
Peso: 5.2
Condições ambientais: -20 to 50DEG C Operating, -40 to 85DEG C Armazenamento, 5 to 95 % Humidade
Marca: PROSOFT
Sub-Categoria: 5000
Tipo: Stand-alone Gateway
The ProLinx Modbus Plus to Modbus TCP/IP Gateway creates a powerful connection between devices on a Modbus TCP/IP network and a Modbus Plus device. This stand-alone DIN-rail mounted protocol gateway provides one Modbus Plus configurable DB9F port and one Ethernet port. The Modbus Plus protocol driver supports both Master and Slave implementations of the protocol on the DB9 Female Modbus Plus port. The Modbus Plus port is fully configurable. The Modbus TCP/IP protocol driver can interface many different protocols into Schneider Electric Quantum processors as well other solutions supporting the protocol. The MNET driver supports Client and Server connections, and when coupled with the Web option provides a web/ftp interface as well.