Porta ethernet (Modulos ethernet only): 10Base-T half duplex RJ45 ConectOu
Link e Activity IndicadOues LED
Electrical Isolamento 1500 V RMS at 50 Hz to 60 Hz fOu 60 s, applied as
specified in section 5.3.2 De IEC 60950: 1991
Ethernet Broadcast StOum Resiliency = less than Ou equal to 5000 [ARP] frames-
per-second e less than Ou equal to 5 minutes duration
Aplicação Portas: Modbus Plus Conector
Two DB9 Fêmea Padrão Modbus Plus Conectores
Porta serial Isolamento: 2500 V RMS port Sinal Isolamento per UL 1577
3000 Vcc min. port to ground e port to logic potência Isolamento
Shipped com Each Unit: Mini-DIN to DB-9M serial cables
4 ft RS-232 Configuração cable
2.5mm Parafusodriver
CD (docs e Configuração utility)
RS-422/485 DB-9 to Parafuso Terminal AdaptOu (1 Ou 4, depending on POutas)
Fonte de Alimentação: 24 Vcc nominal
18 to 32 Vcc allowed
Positive, Negative, GND Terminals
2.5 mm screwdriver blade
Current Load: 500 mA max @ 32 Vcc max
Temperatura de operação: -4° F to 122° F (-20° C to 50° C)
Temperatura de armazenamento: -40° F to 185° F (-40° C to 85° C)
Humidade relativa: 5% to 95% (sem condensação )
Dimensões: Padrão:
5.20 in H x 2.07 in W x 4.52 in D (13.2 cm x 5.25 cm x 11.48 cm)
Estendido:
5.20 in H x 2.73 in W x 4.52 in D
(13.2 cm x 6.934 cm x 11.48 cm)
Indicadores LED: potência e Módulo Status
Aplicação Status
Porta serial Activity
Porta serial Estado de erro
Configuração Porta serial: DB-9M RS-232 only
No hardware handshaking
Marca: PROSOFT
Sub-Categoria: 5000
Tipo: Stand-alone Gateway
Características especiais: Ideal solution for applications where Modbus Conectividade can be used to integrate a DNP 3.0 Master device into a system; The Modbus gateway InSight a powerful Módulo designed com both Master e Slave support, enabling easy Conexão to Outros Modbus Dispositivos (Modicon processors e many Outross).
Aplicação: Manufacturing, Oil e Gas, Electrical potência e Food Processing.
Padrão: ATEX, CE/EMC, Environmental, UL,GOST-R
Ethernet: 10Base-T
Interface: RS-232, RS-422, RS-485
Port: 4
Data Transfer Rate: 110 to 115
Configuração: Yes
Classificação de frequência: 50 to 60
Conectividade: Serial
Protocol: DH485, DNP 3.0
Software Requirements: Drivers
Invólucro: Aluminum
Comprimento: 4.52
Tamanho: 2.07
Peso: 5.2
Condições ambientais: -20 to 50DEG C Operating, -40 to 85DEG C Armazenamento, 5 to 95 % Humidade
The ProLinx DNP 3.0 Slave to Modbus Master/Slave Gateway creates a powerful connection between devices on a Modbus network and a DNP master device. This stand-alone DIN-rail mounted protocol gateway provides one DNP 3.0 Slave configurable serial port, and three Modbus Master or Slave configurable serial ports. The DNP 3.0 Slave protocol driver supports Slave implementations of the protocol on one port. This port is fully configurable. The Modbus protocol driver supports Master and Slave implementations of the protocol. All Modbus serial ports are individually configurable, providing a very powerful and flexible host or device interface solution.