Fonte de Alimentação: 24 Vcc nominal
18 to 32 Vcc allowed
Positive, Negative, GND Terminals
2.5 mm screwdriver blade
Current Load: 500 mA max @ 32 Vcc max
Humidade relativa: 5% to 95% (sem condensação )
Dimensões: Padrão:
5.20 in H x 2.07 in W x 4.52 in D (13.2 cm x 5.25 cm x 11.48 cm)
Estendido:
5.20 in H x 2.73 in W x 4.52 in D
(13.2 cm x 6.934 cm x 11.48 cm)
Indicadores LED: potência e Módulo Status
Aplicação Status
Porta serial Activity
Porta serial Estado de erro
Configuração Porta serial: DB-9M RS-232 only
No hardware handshaking
Porta ethernet (Modulos ethernet only): 10Base-T half duplex RJ45 ConectOu
Link e Activity IndicadOues LED
Electrical Isolamento 1500 V RMS at 50 Hz to 60 Hz fOu 60 s, applied as
specified in section 5.3.2 De IEC 60950: 1991
Ethernet Broadcast StOum Resiliency = less than Ou equal to 5000 [ARP] frames-
per-second e less than Ou equal to 5 minutes duration
Porta serial Isolamento: 2500 V RMS port Sinal Isolamento per UL 1577
3000 Vcc min. port to ground e port to logic potência Isolamento
Shipped com Each Unit: Mini-DIN to DB-9M serial cables
4 ft RS-232 Configuração cable
2.5mm Parafusodriver
CD (docs e Configuração utility)
RS-422/485 DB-9 to Parafuso Terminal AdaptOu (1 Ou 4, depending on POutas)
Aplicação Portas: Modbus Plus Conector
Two DB9 Fêmea Padrão Modbus Plus Conectores
Temperatura de operação: -4° F to 122° F (-20° C to 50° C)
Temperatura de armazenamento: -40° F to 185° F (-40° C to 85° C)
Padrão: ATEX, CE/EMC, Environmental, UL,GOST-R
Data Transfer Rate: 110 to 115
Configuração: Yes
Software Requirements: Drivers
Invólucro: Aluminum
Comprimento: 4.52
Tamanho: 2.07
Peso: 5.2
Condições ambientais: -20 to 50DEG C Operating, -40 to 85DEG C Armazenamento, 5 to 95 % Humidade
Marca: PROSOFT
Sub-Categoria: 5000
Tipo: Stand-alone Gateway
Características especiais: Adds three additional slave Portas for a DF1 based device; Allows users to connect programming sDetware, HMI, e modems to Processadors simultaneously; Commes from the host Dispositivos are passed through the Módulo e routed directly to the front port De the Processador.
Aplicação: Manufacturing, Oil e Gas, Electrical potência e Food Processing.
Ethernet: 10Base-T
Interface: RS-232, RS-422, RS-485
Port: 4
Classificação de frequência: 50 to 60
Conectividade: Serial
Protocol: DF1
The ProLinx DF1 Serial Port Expander Gateway allows you to attach up to three separate DF1 master devices to a single DF1 slave. The module is designed to act as a multiplexer, allowing simultaneous connections from multiple DF1 masters to a single DF1 slave. A common use for the module is to have an HMI panel, SCADA software, and Programming software all communicating to the same DF1 channel 0 port of the Rockwell Automation processor. The module provides a single DF1 Master port and three DF1 Slave ports.