Special Features: Two fully configurable serial ports, each capable of supporting Fisher ROC Master. Support for the storage and transfer of up to 4000 registers to the PLC /SLC data tables. Support movement of binary, integer, ASCII, and floating point data types. Memory mapping is completely user definable through data table configuration. RS-232C handshaking for SCADA radio/modem applications. RS-422/RS-485 compatible for Multi-drop applications with up to 32 slaves per port. Satellite and Packet Radio support with a configurable Inter-character Timeout available per port. Software configuration (From processor ladder logic): Slave Addr: 0 to 255; Parity: None, odd, or even; Stop Bit: 1 or 2; Baud Rate: 300 TO 38,400; RTS to TxD: 0 to 65535 ms, 1 ms resolution; RTS Off: 0 to 65535 ms, 1 ms resolution; Timeout: 0 to 65535 ms, 1 ms resolution. The Fisher ROC Master protocol driver is written in Assembly and in a compiled higher level language. As such, the interrupt capabilities of the hardware are fully utilized to minimize delays, and to optimize the product's performance.
Standard: CUL US, CE
Number Of Channels: 10/100 Base-T
Communication: Fisher ROC
Processor: PLC 5
Enclosure: Aluminium
Display: 2 X 24 Alphanumeric; Clock And Date
Connection Cables: DB-9 cable
Interface: RS-232C, RS-422 and RS-485
Power Supply: 0.65 A
Mounting: Rack
Operating Temperature: 0 to 60°C (32 to 140°F)
Brand Name: PROSOFT
Sub Brand: 3100
Type: Communication Module
The MetOne PCX Water Quality Meter Master Communication Module is a single slot solution for the Rockwell Automation PLC platforms.